DS|POWER H (10-100kVA)

DS|POWER H (10-100kVA)


The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision

GENERAL SPECIFICATIONS
• Transformerless UPS topology
• 3 Level topology
• High input power factor
• High efficiency up to 95%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 512 events memory (512 events 45000 alarms)
• Double conversion
• Clock and calender (battery supported)
• Automatic battery test,remaining battery time indicator
• Temperature compansated charge system (optional)
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional graphical panel
• Optional usb flash memory
• Optional SNMP and MODBUS adaptors
• Full digital structure
• Small footprint
• Ecomode operation (optional)
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input/output voltage/frequency/range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for the PFC
• 3 level battery protection
• High charge current capacity
• Charge/discharge current indicator
• Advanced remote control
• Manufactured according to EC Directive; EN62040
• 2 years warranty

TECHNICIAL SPECIFICATIONS

TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 10
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 9
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57dBA
Weight (kg) 87
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 15
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 13,5
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57dBA
Weight (kg) 87
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 20
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 18
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57dBA
Weight (kg) 91
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 30
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 27
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57dBA
Weight (kg) 100
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 40
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 36
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 173
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 60
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 54
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 197
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 80
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 72
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 209
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 100
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99 (at 100% load)
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 90
Input Voltage regulation 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02%
Efficiency up to 95%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x30 (±30) : 60 pieces
Float charging voltage 2x405 VDC
Float / End of dischg voltage 2x300 VDC
Battery Housing Internal
Battery ambient temp 25ºC
Protection 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 65 dBA
Weight (kg) 220
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at the input & output (internal)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
NOT
(*) Depending on power and input/output conditions
GVoltage tolerance ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan
Genset Kit Standard (programmable)