DS|POWER 300 HT (10-400kVA)

DS|POWER 300 HT (10-400kVA)


GENERAL SPECIFICATIONS
• Low input current total harmonic distortion (THD)
• Galvanic isolation at output
• High input power factor
• High efficiency up to 93,5%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 512 events memory (512 events 45000 alarms)
• Clock and calender (battery supported)
• Automatic battery test,remaining battery time indicator
• Temperature compansated charge system (optional) (opsiyonel)
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional graphical panel
• Optional usb flash memory
• Optional SNMP and MODBUS adaptors
• Manufactured according to EC Directive; EN62040
• Full digital structure
• Small footprint
• Ecomode operation (optional)
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input/output voltage/frequency/range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for the PFC
• 3 level battery protection
• High charge current capacity
• Charge/discharge current indicator
• Advanced remote control
• 2 years warranty

TECHNICIAL SPECIFICATIONS

TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 10
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 9
Power factor 0,9
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 336 VDC (2X28 batteries)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 280 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1 , EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57 dBA
Weight (kg) 187
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 15
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 13,5
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 57 dBA
Weight (kg) 198,5
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 20
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 18
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 244
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 30
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 27
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 270
Dimension (mm) HxWxD 400x815x1040
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 40
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 36
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 62 dBA
Weight (kg) 393
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 60
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 54
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 64 dBA
Weight (kg) 457
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 80
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 72
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 64 dBA
Weight (kg) 536
Dimension (mm) HxWxD 515x855x1440
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 100
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 90
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 68 dBA
Weight (kg) 539
Dimension (mm) HxWxD 825x855x1770
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 120
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 108
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 68 dBA
Weight (kg) 595
Dimension (mm) HxWxD 825x855x1770
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 160
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 144
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 68 dBA
Weight (kg) 647
Dimension (mm) HxWxD 825x855x1770
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 200
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 180
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level < 68 dBA
Weight (kg) 910,5
Dimension (mm) HxWxD 825x855x1770
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 250
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 225
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level 72 dBA
Weight (kg) 1150
Dimension (mm) HxWxD 1250x1055x1900
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 300
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 270
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level 72 dBA
Weight (kg) 1283
Dimension (mm) HxWxD 1250x1055x1900
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 400
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 360
Power factor 0,9 (0,8 and 1 optional)
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number ± 312 VDC (2x26 batts)
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 351 VDC / ± 260 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORS P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm Logging Standard:with time & date 512 events
Protections Power module over-temperature, Overcurrent, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level 72 dBA
Weight (kg) 1497
Dimension (mm) HxWxD 1250x1055x1900
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation Up to 8 units
(*) Depending on power and input/output conditions
TECHNICIAL SPECIFICATIONS
Nominal power (kVA) 500
INPUT
Voltage 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency 50Hz / 60Hz, ± 10%
Power factor (at100% load) ≥ 0.99
THDI (*) ≤ %3
By-Pass Voltage 380/400 VAC 3 Phase + N, ± 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW) 400
Power factor 0.8
Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency 50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load) up to 94%
Output current crest factor 3:1
Overload Protection 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other Protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD ≤ 2% (at 100% linear load)
BATTERIES
Type VRLA AGM / GEL / NiCd
Battery Number 2x28 batteries
Float charging voltage ± 378 VDC
Float / End of dischg voltage ± 280 VDC
Battery Housing External
Battery ambient temp 25ºC
Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic Testing Standard every 72 hours (adjustable)
GENEL
Standards EN62040-1, EN62040-2, EN62040-3
User Interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, Interactive battery panel input, Genset input
Genset Kit Standard (programmable)
Soſtware Standard T-Mon UPS Management Software (3 clients + 1 server management)
Alarm Logging Standard: with time & date 512 events
Protections Power module over-temperature, Over current, Temperature high alarm
Temperature Range 0ºC - 40ºC
Protection class IP20
Relative humidity 90% max. (non-condensing)
Altitude < 1000m above sea level
Noise level 72 dBA
Weight (kg) 2402
Dimension (mm) HxWxD 2020x2250x770
OPTIONS
Input / Output voltage Please ask
Transformer Galvanic isolation transformer at input (optional)
Soſtware T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Comm. adaptors SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel Operation up to 8 units
(*) Depending on power and input/output conditions